Plan Review Notes
Plan Review Notes For Permit 22111267
Permit Number 22111267
Review Stop B
Sequence Number 1
Notes
Date Text
2022-12-13 13:30:001ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. IDENTIFY THE LOCATION OF THE POOL ON THE SURVEY/SITE
 PLAN.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 2.PROVIDE ALARMS
  
 R4501.17.1.9
 WHERE A WALL OF A DWELLING SERVES AS PART OF THE
 BARRIER, ONE OF THE FOLLOWING SHALL APPLY:
  
 1. ALL DOORS AND WINDOWS PROVIDING DIRECT ACCESS FROM
 THE HOME TO THE POOL SHALL BE EQUIPPED WITH AN EXIT
 ALARM COMPLYING WITH UL 2017 THAT HAS A MINIMUM SOUND
 PRESSURE RATING OF 85 DBA AT 10 FEET (3048 MM). ANY
 DEACTIVATION SWITCH SHALL BE LOCATED AT LEAST 54 INCHES
 (1372 MM) ABOVE THE THRESHOLD OF THE ACCESS. SEPARATE
 ALARMS ARE NOT REQUIRED FOR EACH DOOR OR WINDOW IF
 SENSORS WIRED TO A CENTRAL ALARM SOUND WHEN CONTACT IS
 BROKEN AT ANY OPENING.
  
 2. ALL DOORS PROVIDING DIRECT ACCESS FROM THE HOME TO
 THE POOL MUST BE EQUIPPED WITH A SELF-CLOSING,
 SELF-LATCHING DEVICE WITH POSITIVE MECHANICAL
 LATCHING/LOCKING INSTALLED A MINIMUM OF 54 INCHES (1372
 MM) ABOVE THE THRESHOLD, WHICH IS APPROVED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.