| 2022-12-15 11:57:42 | 1ST REVIEW FMC |
| | PERMIT: 22111266 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) THIS SUBMISSION IS NOT COMPLETE. THIS REVIEWER |
| | CANNOT COMPLETE THE MECHANICAL AUDIT AT THIS TIME. THIS |
| | IS THE HOOD PERMIT FOR ALL KITCHEN HOODS, GREASE DUCTS |
| | AND MAKE-UP AIR FOR EACH. PLEASE SUBMIT DRAWINGS |
| | IDENTIFYING EACH HOOD IN THE KITCHEN, THE TERMINATION |
| | LOCATIONS WITH DETAILS SHOWING CLEARANCE COMPLIANCES, |
| | THE GREASE DUCT DRAWINGS THAT INCLUDE THE SIZES, |
| | CLEARANCES TO COMBUSTIBLES, CLEAN OUT LOCATIONS, THE |
| | MAKE-UP AIR DUCT WORK INCLUDING THE SIZES AND LOCATION |
| | OF THE MAKE-UP AIR UNITS. FBC 107.3.5 |
| | |
| | 2) PLEASE SHOW THAT THE IN-LINE KITCHEN EXHAUST FANS |
| | SHOWN ON THE MECHANICAL DRAWING WILL MEET THE |
| | PROTECTION REQUIREMENTS OF FMC 506.5.1.2. |
| | |
| | 3) THE VALUE ON THE PERMIT APPLICATION SEEMS VERY LOW, |
| | PLEASE ADJUST THE VALUE TO INCLUDE ALL THE WORK LISTED |
| | ABOVE. |
| | |
| | 4) CAPTIVE-AIRE DRAWING SHEET NO. 5: THIS DRAWING |
| | INDICATES THE HOOD FRONT DOES NOT MEET THE REQUIREMENTS |
| | IN FMC 507.4.1. PLEASE EXPLAIN WHAT APPLIANCE THAT WILL |
| | BE UNDER THIS HOOD. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |