2022-12-15 11:57:421ST REVIEW FMC
 PERMIT: 22111266
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) THIS SUBMISSION IS NOT COMPLETE. THIS REVIEWER
 CANNOT COMPLETE THE MECHANICAL AUDIT AT THIS TIME. THIS
 IS THE HOOD PERMIT FOR ALL KITCHEN HOODS, GREASE DUCTS
 AND MAKE-UP AIR FOR EACH. PLEASE SUBMIT DRAWINGS
 IDENTIFYING EACH HOOD IN THE KITCHEN, THE TERMINATION
 LOCATIONS WITH DETAILS SHOWING CLEARANCE COMPLIANCES,
 THE GREASE DUCT DRAWINGS THAT INCLUDE THE SIZES,
 CLEARANCES TO COMBUSTIBLES, CLEAN OUT LOCATIONS, THE
 MAKE-UP AIR DUCT WORK INCLUDING THE SIZES AND LOCATION
 OF THE MAKE-UP AIR UNITS. FBC 107.3.5
  
 2) PLEASE SHOW THAT THE IN-LINE KITCHEN EXHAUST FANS
 SHOWN ON THE MECHANICAL DRAWING WILL MEET THE
 PROTECTION REQUIREMENTS OF FMC 506.5.1.2.
  
 3) THE VALUE ON THE PERMIT APPLICATION SEEMS VERY LOW,
 PLEASE ADJUST THE VALUE TO INCLUDE ALL THE WORK LISTED
 ABOVE.
  
 4) CAPTIVE-AIRE DRAWING SHEET NO. 5: THIS DRAWING
 INDICATES THE HOOD FRONT DOES NOT MEET THE REQUIREMENTS
 IN FMC 507.4.1. PLEASE EXPLAIN WHAT APPLIANCE THAT WILL
 BE UNDER THIS HOOD.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  