Plan Review Notes
Plan Review Notes For Permit 22111266
Permit Number 22111266
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-12-05 14:32:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A HOOD INSTALLATION.
  
 THERE ARE NO INDICATIONS OF THE VENTING SYSTEM.
  
 PER NFPA 96
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EX HAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT
 AND PERFOR MANCE REQUIREMENTS OF THIS STANDARD.
  
 PLEASE PROVIDE DETAILS OF THE REQUIRED SYSTEM IN
 COMLIANCE WITH NFPA.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  