| 2023-07-12 11:33:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF SCOPE OF WORK ON THE COVER |
| | SHEET, HOWEVER, THE SUBMITTED FLOOR PLAN DOES NOT |
| | REFLECT THAT SCOPE OF WORK. |
| | |
| | WHAT IS THE EXTENT AND DETAIL OF THE INTERIOR |
| | PARTITION? I.E. WHAT IS EXISTING AND WHAT IS NEW |
| | CONSTRUCTION? |
| | |
| | THERE IS A REFERENCE TO A MINI SPLIT(SEE MECH. PLAN) |
| | BUT THERE IS NO MECHANICAL PLAN. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE GREATER DETAIL |
| | OD THE WALL AND A MECHANICAL PLAN IN AGREEMENT OF THE |
| | SCOPE OF WORK. |
| | |
| | |
| | |
| | 2) THERE IS REFENCE TO WALL CONSTRUCTION IN A BUILDING |
| | WITH A FIRE SPRINKLER. |
| | |
| | DUE TO THE DEMO & CONSTRUCTION IT REQUIRES AND |
| | EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS |
| | FOR CODE COMPLIANT COVERAGE PER NFPA 13 & 72. |
| | |
| | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING |
| | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP |
| | DRAWINGS, IN COMPLIANCE WITH NFPA 13 & 72 |
| | |
| | PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| | NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |