Plan Review Notes
Plan Review Notes For Permit 22111264
Permit Number 22111264
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-07-12 11:33:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF SCOPE OF WORK ON THE COVER
 SHEET, HOWEVER, THE SUBMITTED FLOOR PLAN DOES NOT
 REFLECT THAT SCOPE OF WORK.
  
 WHAT IS THE EXTENT AND DETAIL OF THE INTERIOR
 PARTITION? I.E. WHAT IS EXISTING AND WHAT IS NEW
 CONSTRUCTION?
  
 THERE IS A REFERENCE TO A MINI SPLIT(SEE MECH. PLAN)
 BUT THERE IS NO MECHANICAL PLAN.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE GREATER DETAIL
 OD THE WALL AND A MECHANICAL PLAN IN AGREEMENT OF THE
 SCOPE OF WORK.
  
  
  
 2) THERE IS REFENCE TO WALL CONSTRUCTION IN A BUILDING
 WITH A FIRE SPRINKLER.
  
 DUE TO THE DEMO & CONSTRUCTION IT REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE PER NFPA 13 & 72.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS, IN COMPLIANCE WITH NFPA 13 & 72
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  