Plan Review Notes
Plan Review Notes For Permit 22111253
Permit Number 22111253
Review Stop M
Sequence Number 1
Notes
Date Text
2023-04-14 10:55:191ST REVIEW FMC
 PERMIT: 22111253
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE DETAILS FOR THE VENTILATION OF THIS
 PENTHOUSE. EACH OCCUPIED SPACE SHALL BE VENTILATED BY
 NATURAL MEANS OR BY MECHANICAL MEANS. THE WINDOWS DO
 NOT APPEAR TO OPEN. FMC 401.2
  
 2) EACH BATHROOM EXHAUST SHALL BE PROVIDED ACCESS FOR
 MAINTENANCE AND CHANGE OUT. FMC 306.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  