Plan Review Notes
Plan Review Notes For Permit 22111251
Permit Number 22111251
Review Stop P
Sequence Number 3
Notes
Date Text
2023-04-17 15:03:222ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. CORRECTION DOES NOT COMPLY - THE MIXING VALVE MUST
 BE INSTALLED AT THE HOT WATER SOURCE, NOT AT THE MOP
 SINK. 2020 FPC 613.1
  
 CORRECTION DOES NOT FULLY COMPLY WITH THE CODE SECTION
 - "ALL" HOT WATER MUST BE LIMITED BY A MIXING VALVE. IF
 YOU WANT 140 AS WELL AS 120, THEN TWO MIXING VALVES ARE
 NEEDED. CURRENTLY, THE 140 GOING TO THE MOP SINK IS
 ONLY LIMITED BY THE THERMOSTAT ON THE WATER HEATER. PER
 THE CODE SECTION - "THE THERMOSTAT FOR THE WATER HEATER
 SHALL NEVER BE THE LIMITING DEVICE FOR HOT AND/OR
 TEMPERED WATER DELIVERY".
 PROVIDE A TEMPERATURE-ACTUATED MIXING VALVE COMPLYING
 WITH ASSE 1017 AT THE WATER HEATER. FBC PL 607.1.1,
 613.1
  
 4. DONE
  
 5. DONE
  
 6. DONE
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  