2023-03-07 06:58:422ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. CORRECTION DOES NOT FULLY COMPLY WITH THE CODE
 SECTION - "ALL" HOT WATER MUST BE LIMITED BY A MIXING
 VALVE. IF YOU WANT 140 AS WELL AS 120, THEN TWO MIXING
 VALVES ARE NEEDED. CURRENTLY, THE 140 GOING TO THE MOP
 SINK IS ONLY LIMITED BY THE THERMOSTAT ON THE WATER
 HEATER. PER THE CODE SECTION - "THE THERMOSTAT FOR THE
 WATER HEATER SHALL NEVER BE THE LIMITING DEVICE FOR HOT
 AND/OR TEMPERED WATER DELIVERY".
 PROVIDE A TEMPERATURE-ACTUATED MIXING VALVE COMPLYING
 WITH ASSE 1017 AT THE WATER HEATER. FBC PL 607.1.1,
 613.1
  
 4. DONE
  
 5. DONE
  
 6. DONE
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR