| 2022-12-28 14:48:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A 401 LIIFE SAFETY - THERE IS AN INDICATION OF |
| | AN EXIT SIGN OVER A REAR DOOR LEADING INTO THE STORAGE |
| | 106 ROOM. |
| | |
| | THAT SINGLE EXIT DOOR SWINGS AGAINST THE PATH OF EXIT |
| | TRAVEL. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE PROVIDE THE OCCUPANCY LOAD INDICATING COMPLIANCE |
| | WITH (1) OR CORRECT. |
| | |
| | 1A) THE REAR EXIT DOOR NOTED ABOVE LEADS INTO A STORAGE |
| | ROOM LEADING TO A DOUBLE DOOR EXIT DISCHARGE. |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE CON STRUED AS INTERVENING ROOMS. EXIT |
| | ACCESS SHALL BE ARRANGED SO THAT IT IS |
| | NOT NECESSARY TO PASS THROUGH ANY AREA IDENTIFIED UNDER |
| | PROTECTION FROM |
| | HAZARDS IN CHAPTERS 11 THROUGH 43 |
| | |
| | THE PROPOSED OCCUPANCY CLASSIFICATION APPEARS TO BE |
| | MERCANTILE. |
| | |
| | PER NFPA 101 CH 36 |
| | |
| | 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE |
| | OCCUPANCIES |
| | THAT ARE PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), AND |
| | EXIT ACCESS IN ALL |
| | CLASS C MERCANTILE OCCUPANCIES, SHALL BE PERMITTED TO |
| | PASS THROUGH |
| | STOREROOMS, PROVIDED THAT ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE |
| | PROVIDED THROUGH |
| | THE STOREROOM. |
| | (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING. |
| | (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT |
| | LESS THAN 44 IN. |
| | (1120 MM) WIDE. |
| | (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE |
| | DEFINED, DIRECT, |
| | AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED |
| | CONDITION. |
| | |
| | PLEASE PROVIDE PROVIDE DETAILS TO IN COMPLAINCE WITH |
| | THE CODE OR THAT SINGLE SWING DOOR CANNOT BE USED AS AN |
| | EXIT THROUGH THE STORAGE ROOM. |
| | |
| | |
| | |
| | 2) SHEET A 302 - THERE IS AN INDICATION OF A DOOR |
| | SCHEDULE; HOWEVER, THERE ARE NO INDICATIONS OF |
| | LOCKS/LATCHES/DOOR CLOSURES, ETC SHOWING COMPLIANCE ON |
| | EIXT DOORS WITH NFPA 101, CH 7 MEANS OF EGRESS. |
| | |
| | PER NFPA 101 |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES |
| | |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE |
| | PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF OPERATION |
| | AND THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. |
| | |
| | PLEASE PROVIDE DETAILS AND/OR A NOTE OF ACKNOWLEDGMENT |
| | TO COMPLY WITH NFPA 101(VERIFIED ON FIRE INSPECTION) |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |