| Date |
Text |
| 2023-01-11 14:20:34 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 22111251 1813 S DIXIE HWY |
| | |
| | 1ST REVIEW |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.A402, A101: CLEARANCE AROUND A FLOOR MOUNTED WATER |
| | CLOSET SHALL BE 60 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE SIDE WALL AND 59 INCHES DEEP |
| | MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED |
| | PERPENDICULAR TO THE REAR WALL PER FBC ACC 604.8.1.1. |
| | |
| | 2. P0.1/PLUMBING SPECIFICATION NOTE 24: TO SHOW |
| | COMPLIANCE WITH FBC EC C403.2.10, TABLE 403.2.10, |
| | PLEASE ADD TO NOTE "HOT WATER INSULATION THICKNESS |
| | SHALL BE MINIMUM 1 INCH" |
| | |
| | 3. PROVIDE A TEMPERATURE-ACTUATED MIXING VALVE |
| | COMPLYING WITH ASSE 1017 AT THE WATER HEATER. FBC PL |
| | 607.1.1, 613.1 |
| | |
| | 4. PROVIDE A TRAP SEAL PROTECTION SPECIFICATION AND |
| | DETAIL COMPLYING WITH ONE OF THE FOLLOWING: FBC |
| | 1002.4.1.1, 1002.4.1.2, 1002.4.1.3 OR 1002.4.1.4. |
| | |
| | 5. P0.1, P1.1/ SANITARY RISER, SANITARY PLAN VIEW: |
| | FLOOR DRAIN IN RESTROOM #103 SHALL CONNECT TO THE WET |
| | VENT, NOT THE WATER CLOSET FIXTURE DRAIN. FBC PL 912.1 |
| | |
| | 6. P0.1/SANITARY RISER: MOP SINK DRAIN SHALL NOT BE |
| | S-TRAPPED; SLOPE FROM TRAP TO VENT SHALL NOT EXCEED THE |
| | REQUIREMENTS OF FBC PL 909.1, 909.2, 1002.3 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |
| | |