Plan Review Notes
Plan Review Notes For Permit 22111251
Permit Number 22111251
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-11 14:20:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 22111251 1813 S DIXIE HWY
  
 1ST REVIEW
  
  
 PLUMBING COMMENTS: DENIED
  
 1.A402, A101: CLEARANCE AROUND A FLOOR MOUNTED WATER
 CLOSET SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 59 INCHES DEEP
 MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED
 PERPENDICULAR TO THE REAR WALL PER FBC ACC 604.8.1.1.
  
 2. P0.1/PLUMBING SPECIFICATION NOTE 24: TO SHOW
 COMPLIANCE WITH FBC EC C403.2.10, TABLE 403.2.10,
 PLEASE ADD TO NOTE "HOT WATER INSULATION THICKNESS
 SHALL BE MINIMUM 1 INCH"
  
 3. PROVIDE A TEMPERATURE-ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1017 AT THE WATER HEATER. FBC PL
 607.1.1, 613.1
  
 4. PROVIDE A TRAP SEAL PROTECTION SPECIFICATION AND
 DETAIL COMPLYING WITH ONE OF THE FOLLOWING: FBC
 1002.4.1.1, 1002.4.1.2, 1002.4.1.3 OR 1002.4.1.4.
  
 5. P0.1, P1.1/ SANITARY RISER, SANITARY PLAN VIEW:
 FLOOR DRAIN IN RESTROOM #103 SHALL CONNECT TO THE WET
 VENT, NOT THE WATER CLOSET FIXTURE DRAIN. FBC PL 912.1
  
 6. P0.1/SANITARY RISER: MOP SINK DRAIN SHALL NOT BE
 S-TRAPPED; SLOPE FROM TRAP TO VENT SHALL NOT EXCEED THE
 REQUIREMENTS OF FBC PL 909.1, 909.2, 1002.3
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved