2022-12-15 14:32:29ELECTRIC REVIEW PASSED
  
 12/20/22 PREVIOUS COMMENT ADDRESSED. CUSTOMER EMAILED
 SPECS ON RAYCAP PANEL AND I UPLOADE INTO DRAWINGS
 FOLDER. MP
  
 1) IT APPEARS YOU HAVE REMOVED THE CIRCUIT BREAKER
 PANEL IN PLACE OF THE RAYCAP PANEL. IT IS REQUIRED TO
 BE A SERVICE RATED PANEL. IN ADDITION, THE MAIN IS ALSO
 LISTED AS BOTH 70 AND 60 AMP. PLEASE PROVIDED
 SPECIFICATIONS DETAILING SERVICE RATING LISTING FOR
 RAYCAP PANEL AND CORRECT DISCREPANCY FOR MAIN BREAKER.
 NEC 110.3 NEC 230.66 AND NEC 215.5
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  