2023-01-06 08:05:271ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FAC 604.5 GRAB BARS - THE GRAB BARS DETAILED
 ARE NOT IN COMPLIANCE WITH THE ACCESSIBILITY CODE. SIDE
 WALL GRAB BAR IS TO BE 42" MIN, AND BETWEEN 33 AND 36
 ABOVE THE FLOOR. REAR WALL IS TO BE 36" MIN, AND
 BETWEEN 33 AND 36 ABOVE THE FLOOR.
  
 2. 2020 FAC 604.3.1 - THE CLEARANCE AROUND THE WATER
 CLOSET SHALL BE 60" FROM THE SIDE WALL AND 56" FROM THE
 BACK WALL, CLEAR FLOOR SPACE FOR ACCESS.
  
 3. 2020 FAC 604.2 - PAGE 4, DETAIL 1;S3 APPEARS TO SHOW
 A MEASUREMENT OF 18" TO THE EDGE OF THE WATER CLOSET.
 THE ADA WATER CLOSET IS TO BE 16" TO 18" FROM THE SIDE
 WALL TO CENTER.
  
 4. 2020 FPC 607.1.2/419.5 - SHOW A DETAIL THAT INCLUDES
 A TEMPERING VALVE FOR COMPLIANCE WITH THIS SECTION.
  
 PLEASE REVIEW AND ADDRESS ALL ADA MEASUREMENTS TO
 VERIFY COMPLIANCE.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved