| 2023-01-25 11:11:52 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22111176 |
| | ADD: 424 PARK PLACE # 422 PCN: 74-43-43-28-06-001-0011 |
| | CONT: LEGACY CONSTRUCTIONN SERVICES OHIO |
| | TEL: 561-797-5274 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 25/2023 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A OVERALL FLOOR PLAN OF THIS BUILDING |
| | WHERE WORK IS TO OCCUR IN THIS BUILDING. AN ADDRESS |
| | STOP IS BEING ADDED TO THE PLAN REVIEW SCREEN. THE |
| | COUNTY MY GEO NAV SHOWS TENANT SPACES 101-108. |
| | |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED. |
| | |
| | 2) THE PERMIT APPLICATION DESCRIPTION OF WORK IS LEFT |
| | BLANK, THE DOLLAR AMOUNT GIVEN FOR THIS PERMIT IS |
| | $7,500.00 DOLLARS. 2020 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. THE TITLE SHEET STATES NEW |
| | MEZZANINE. |
| | |
| | 3) ROW HOUSE IMPROVEMENTS. IS WHAT WAS ASSIGNED TO THE |
| | PURPOSE OF THIS PERMIT. THE COVERSHEET ALSO STATES ROW |
| | HOUSE TENANT IMPROVEMENTS, IT WOULD APPEAR THIS IS |
| | GOING TO BE SOME RESIDENTIAL USE? |
| | |
| | 4) SHEET S1 DIMENSION FLOOR PLAN, THE DESIGN CRITERIA |
| | LIST THE CONSTRUCTION TYPE AS TYPE II, OCCUPANCY TYPE |
| | AS BUSINESS, BASE AREA AS 1305 SQ. FT. NEW ADDITIONAL |
| | SQ. FT. 392 SQ. FT. AND ALTERATION TYPE LEVEL 2. |
| | MISSING INFORMATION IS THE BUILDING FIRE SPRINKLERED OR |
| | NOT. |
| | |
| | 4A) THE FLOOR PLAN DOES NOT REPRESENT THE 1305 SQ. FT |
| | OF FOOTAGE ON THE FIRST FLOOR TO SCALE VERSES THE NEW |
| | SQ. FOOTAGE OF THE MEZZANINE. 107.2.1.3. QUALITY OF |
| | PLANS. BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH |
| | SCALE ON SUBSTANTIAL PAPER OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT |
| | POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS |
| | IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM |
| | SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED |
| | TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE |
| | COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA |
| | STATUTES. ALSO SEE SECTION 505.2.1 AREA LIMITATIONS AND |
| | EXCEPTIONS. |
| | |
| | 4B) THE DESIGNER OF RECORD LIST THIS BUILDING AS TYPE |
| | II CONSTRUCTION. PLEASE PROVIDE THE ROOF FRAMING AND |
| | DECKING MATERIAL FOR THIS BUILDING BUILT IN 1950. TABLE |
| | 601 CONSTRUCTION TYPE II IS THIS TYPE A OR B |
| | CONSTRUCTION. |
| | |
| | 4C) THE NEW MEZZANINE PLEASE PROVIDE THE USEAGE AND |
| | OCCUPANT LOAD FOR THE NEW MEZZANINE. MISSING |
| | INFORMATION MINIMUM PLAN REVIEW CRITERIA 107.3.5. |
| | |
| | 4D) PLEASE PROVIDE THE FLOOR LOADING FOR THE MEZZANINE, |
| | LIVE FLOOR LOADS AND THE LIVE FLOOR LOADS FOR THE |
| | PROPOSED STAIRWAY. 2020 FBC-BUILDING. TABLE 1607. 1. |
| | |
| | 4E) IT APPEARS WITH THE NEW FIRST FLOOR BENEATH THE |
| | PROPOSED MEZZANINE THERE IS A NEW RESTROOM AND ROOM |
| | THAT IS NOT IDENTIFIED. THERE IS A SECOND ROOM BENEATH |
| | THE STAIRS NOT IDENTIFIED AS USEAGE. 2020 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL |
| | BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. PLEASE REVIEW 2020 |
| | FBC-BUILDING CODE SECTION 1011.7.3. |
| | |
| | 4F) THE STAIRS DO NOT INDICATE WHAT MATERIAL THE |
| | STRINGERS GOING TO BE MADE NOR RISERS AND TREADS. 2020 |
| | W. P. B. ADMINISTRATIVE CODE107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA |
| | |
| | 4G) MISSING GUARDRAIL AND HANDRAIL DESIGN CRITERIA |
| | 1607.8.1., HANDRAILS SECTION 1014 AND GUARDS SECTION |
| | 1015. |
| | |
| | 5) SHEET S2 DETAIL 5 SHOWS A LOAD BEARING WALL WITH A |
| | EXISTING SLAB AND MONOLITHIC FOOTER. THE NEW BEARING |
| | WALL ONLY HAS A 4 INCH CONCRETE SLAB, DISCREPANCY. 2020 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 6A) SHEET S-3 PLEASE REVIEW THE HEIGHT AS SHOWN FOR 8 |
| | FEET IT APPEARS TO BE ABOUT A FOOT ABOVE FINISH FLOOR. |
| | THAT WOULD MAKE THE HEIGHT UNDER THE MEZZANINE ABOUT |
| | 6FEET 2 INCHES, TYPO. PLEASE CORRECT. |
| | |
| | 6B) THE ISOMETRIC RESTROOM LAYOUT IS OPPOSITE THE FLOOR |
| | PLAN S1. DISCREPANCY IN PLANS. |
| | |
| | 6C) E) HEIGHT OF THE WATERCLOSET SEATS FROM FINISH |
| | FLOOR. SECTION 604.4. |
| | |
| | 6D) HEIGHT OF THE LAVATORIES AND OR SINKS OR COUNTER |
| | SURFACES FROM THE FINISH FLOOR. SECTION 606.3. |
| | |
| | 6E) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE BOTTOM EDGE OF THE REFLECTIVE SURFACE, MIRRORS |
| | ABOVE SINKS. SECTION 606.3. |
| | 6F) LOCATIONS, LENGTHS AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS SEE SECTION 604.5, 609.4 &. |
| | FIGURE 604. |
| | 6G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS. |
| | SECTION 604.6. |
| | |
| | 8H) CENTERLINES OF THE TOILET DISPENSER MEASURED FROM |
| | THE FRONTS OF THE WATER CLOSET. SECTION & FIGURE 604.7 |
| | |
| | 7) DEPENDING ON THE OCCUPANT LOAD VERTICAL |
| | ACCESSIBILITY TO THE NEW MEZZANINE. 201.1.1 |
| | 2020FBC-ACCESSIBILITY CODE. |
| | |
| | 8) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |