Plan Review Notes
Plan Review Notes For Permit 22111124
Permit Number 22111124
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-14 14:36:27ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE MORE DETAIL AS TO THE BAPTISTRY AREA.
 THE ELECTRIC WALL AND FLOOR RECTACLES NEARBY MAY BE
 REQUIRED TO BE GFI PROTECTED AND ADDITIONAL GROUNDING
 MAY BE REQUIRED. FBC 107.2
 2) PLEASE PROVIDE GFI PROTECTION FOR MENS ROOM
 RECEPTACLE AND WATER FOUNTAIN AS REQUIRED PER NEC
 210.8(B)(5) AND NEC 422.5(A)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  