2022-12-01 17:40:291ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22111093
 12/1/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1 & P-2: THE PLANS SHOW TWO DWELLINGS ON
 THE SAME LOT WHICH WILL REQUIRE WATER USERS TO INSTALL
 A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF
 DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL
 BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST
 PALM CROSS UTILITIES DEPARTMENT AND SECS. C, D, & E WPB
 CROSS-CONNECTION MANUAL.
  
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 2) P1 & P2: PROVIDE A CLEANOUT AT THE JUNCTION OF THE
 GUEST HOUSE BUILDING DRAIN AND SEWER- SEC. P3005.2.3
 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  