| 2022-12-01 17:40:29 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22111093 |
| | 12/1/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-1 & P-2: THE PLANS SHOW TWO DWELLINGS ON |
| | THE SAME LOT WHICH WILL REQUIRE WATER USERS TO INSTALL |
| | A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF |
| | DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL |
| | BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST |
| | PALM CROSS UTILITIES DEPARTMENT AND SECS. C, D, & E WPB |
| | CROSS-CONNECTION MANUAL. |
| | |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 2) P1 & P2: PROVIDE A CLEANOUT AT THE JUNCTION OF THE |
| | GUEST HOUSE BUILDING DRAIN AND SEWER- SEC. P3005.2.3 |
| | FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |