| 2023-01-25 10:23:25 | FBC-0202 RES. FUEL GAS REVIEW. |
| | PERMIT- 22111092 |
| | 1/25/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P1 & P2 ARE NOT DIGITALLY SIGNED AND SEALED |
| | BY THE ARCHITECT OF RECORD- FL. STATUTE 481.221 AND |
| | SEC. 61G1-16.005 FAC. |
| | |
| | 2) SHEET P2 GAS RISER: THE PVC SLEEVES SPECIFIED FOR |
| | THE PE PIPING ARE NOT APPROVED. REFER TO SEC. |
| | G2415.17.1 & G2415.17.2 FBC RES AND PROVIDE ANODELESS |
| | RISERS OR SERVICE HEAD ADAPTER RISERS FOR THE PE |
| | PIPING. PLESASE NOTE ANODELESS RISERS AND TRANSITION |
| | FITTINGS BETWEEN THE PE AND METALLIC PIPING SHALL |
| | CONFORM TO ASTM D2513 CAT. 1 OR ASTM F1973 - SECS. |
| | G2415.17.1 & G2415.17.2. |
| | |
| | 3) SHEET P2: PLEASE CORRECT THE 11 IN.WC. MAX PRESSURE |
| | FOR THE TAKAGI WATER HEATERS. THE MAN. SPECS INDICATE |
| | MAX 10.5 IN. W.C.- SEC. G2448.1 FBC RES. |
| | |
| | 4) P2 GAS RISER: PLEASE CORRECT THE 2LB. SYSTEM LABEL |
| | TO INDICATE A LOW PRESSURE LESS THAN 2PSI SYSTEM BASED |
| | ON THE PIPE SIZING TABLE 402.4(2) SPECIFIED ON THE |
| | DRAWING- SEC. G2413.3 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |