2023-01-13 08:15:542ND REVIEW FMC
 PERMIT: 22111092
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS REVISION HAS A NEW POOL HOUSE. THIS WILL
 REQUIRE A SEPARATE PERMIT. FBC 107.3.5
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR THE NEW
 POOL HOUSE. FEC R403.7.1
  
 3) SHOW THAT THE TRANSFER GRILLES FOR RETURN AIR FROM
 THE BEDROOM AREA WILL MEET FRC M1602.3 EXCEPTION 1. 1.5
 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY DUCT
 ENTERING THE ROOM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  