| 2023-01-13 08:15:54 | 2ND REVIEW FMC | | | PERMIT: 22111092 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS REVISION HAS A NEW POOL HOUSE. THIS WILL | | | REQUIRE A SEPARATE PERMIT. FBC 107.3.5 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR THE NEW | | | POOL HOUSE. FEC R403.7.1 | | | | | | 3) SHOW THAT THE TRANSFER GRILLES FOR RETURN AIR FROM | | | THE BEDROOM AREA WILL MEET FRC M1602.3 EXCEPTION 1. 1.5 | | | TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY DUCT | | | ENTERING THE ROOM. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|