2023-01-13 10:03:062ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22111092
 1/3/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2: THE GAS RISER SHOWS A 2LB METER, OR 2PSI,
 HOWEVER THE NEW GAS PIPING NOTES ON THE PLAN REFERENCE
 TABLE 402.4(2) WHICH IS A SIZING TABLE FOR LOW PRESSURE
 (LESS THAN 2PSI) SCHED. 40 METALLIC. USING THE SIZING
 TABLE AND THE 72 FT. DEVELOPED LENGTH OF THE SYSTEM THE
 3/4-INCH BRANCH LINE FROM THE TEE TO THE 199 MBH WATER
 HEATER SHALL BE INCREASED TO MINIMUM 1-INCH, AND THE
 3/4-INCH SUPPLYING THE 120 MBH WATER HEATER SHALL BE
 INCREASED TO 1-INCH. THE 1/2-INCH PIPE TO THE DRYER IS
 SIZED ADEQUATELY.
  
 1) SHEET M-1: THE COMBUSTION AIR THROUGH THE WALL VENTS
 ARE NOT DESIGNED IN COMPLIANCE WITH SEC. G2407.5.3.1
 (304.5.3.1) FBC RES WHICH STATES EACH OPENING SHALL BE
 NOT LESS THAN 100 SQUARE INCHES. THE 6X18 INCH LOUVERS
 ALLOW ONLY 75 % FREE AREA OR 81 SQ. INCHES- SEC.
 G2407.10 (304.10). PLEASE INCREASE THE SIZE OF THE
 LOUVERS TO MEET COMPLIANCE. PLEASE NOTE A MINIMUM 1000
 CU. FT. INDOOR AIR VOLUME IS REQUIRED FOR COMBUSTION
 AIR FOR THE DRYER- 2ND REQUEST TO PROVIDE THE
 CALCULATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  