| 2023-01-13 10:03:06 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22111092 |
| | 1/3/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2: THE GAS RISER SHOWS A 2LB METER, OR 2PSI, |
| | HOWEVER THE NEW GAS PIPING NOTES ON THE PLAN REFERENCE |
| | TABLE 402.4(2) WHICH IS A SIZING TABLE FOR LOW PRESSURE |
| | (LESS THAN 2PSI) SCHED. 40 METALLIC. USING THE SIZING |
| | TABLE AND THE 72 FT. DEVELOPED LENGTH OF THE SYSTEM THE |
| | 3/4-INCH BRANCH LINE FROM THE TEE TO THE 199 MBH WATER |
| | HEATER SHALL BE INCREASED TO MINIMUM 1-INCH, AND THE |
| | 3/4-INCH SUPPLYING THE 120 MBH WATER HEATER SHALL BE |
| | INCREASED TO 1-INCH. THE 1/2-INCH PIPE TO THE DRYER IS |
| | SIZED ADEQUATELY. |
| | |
| | 1) SHEET M-1: THE COMBUSTION AIR THROUGH THE WALL VENTS |
| | ARE NOT DESIGNED IN COMPLIANCE WITH SEC. G2407.5.3.1 |
| | (304.5.3.1) FBC RES WHICH STATES EACH OPENING SHALL BE |
| | NOT LESS THAN 100 SQUARE INCHES. THE 6X18 INCH LOUVERS |
| | ALLOW ONLY 75 % FREE AREA OR 81 SQ. INCHES- SEC. |
| | G2407.10 (304.10). PLEASE INCREASE THE SIZE OF THE |
| | LOUVERS TO MEET COMPLIANCE. PLEASE NOTE A MINIMUM 1000 |
| | CU. FT. INDOOR AIR VOLUME IS REQUIRED FOR COMBUSTION |
| | AIR FOR THE DRYER- 2ND REQUEST TO PROVIDE THE |
| | CALCULATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |