| Plan Review Notes For Permit 22111092 |
| Permit Number |
22111092 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-01 16:09:13 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. SERVICE RECEPTACLE | | | A SERVICE RECEPTACLE NEEDS TO BE INSTALLED NEAR THE | | | EQUIPMENT FOR THIS PURPOSE. A 125-VOLT, 15- AND | | | 20-AMPERE RECEPTACLE FOR SERVICING AIR-CONDITIONING AND | | | REFRIGERATION EQUIPMENT IS REQUIRED TO BE LOCATED NOT | | | LESS THAN 7.5 M (25 FT) FROM, | | | AND ON THE SAME LEVEL AS, THE EQUIPMENT ITSELF. THE | | | RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES NEC 210.63 OR IRC | | | E3901.11 | | | | | | END OF COMMENTS | | | | | | THANK YOU, | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | | | | |
|