2022-12-01 16:09:13FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. SERVICE RECEPTACLE
 A SERVICE RECEPTACLE NEEDS TO BE INSTALLED NEAR THE
 EQUIPMENT FOR THIS PURPOSE. A 125-VOLT, 15- AND
 20-AMPERE RECEPTACLE FOR SERVICING AIR-CONDITIONING AND
 REFRIGERATION EQUIPMENT IS REQUIRED TO BE LOCATED NOT
 LESS THAN 7.5 M (25 FT) FROM,
 AND ON THE SAME LEVEL AS, THE EQUIPMENT ITSELF. THE
 RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES NEC 210.63 OR IRC
 E3901.11
  
 END OF COMMENTS
  