| 2022-12-14 13:45:20 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. |
| | NEC 215.2, 220, 408.30 |
| | |
| | 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON |
| | MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN |
| | ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315 |
| | |
| | 3. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER |
| | NEC 440.14 OR IRC E4101.5 |
| | DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN |
| | SIGHT FROM AND READILY ACCESSIBLE??? FROM THE |
| | AIR-CONDITIONING EQUIPMENT. |
| | |
| | 4. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 |
| | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION |
| | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS |
| | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING |
| | OCCUPANCIES |
| | |
| | 5. A ONE-LINE DIAGRAM SHOWINGS SERVICE EQUIPMENT, |
| | SERVICE-ENTRANCE CONDUCTORS, SERVICE DISCONNECT, |
| | SERVICE OVERCURRENT PROTECTION, MAIN POWER FEEDER, |
| | FEEDER CONDUCTORS, PANELBOARDS A AND B, MAIN BONDING |
| | JUMPER, AND GROUNDING ELECTRODE |
| | CONDUCTOR PER NEC 230 AND 250 |
| | |
| | END OF COMMENTS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |