| 2022-12-05 11:40:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE PREVIOUS INDICATIONS THAT THIS ADDRESS |
| | UNDER WENT AN OCCUPANCY CLASSIFICATION CHANGE TO |
| | EDUCATIONAL. |
| | |
| | THERE ARE ALSO INDICATIONS THAT THISS BUILDING IS |
| | OCCUPIED ON THE 1ST FLOOR BY STUDENTS AND TEACHERS PER |
| | THE OCCUPANCY CLASSIFICATION CHANGE. |
| | |
| | THERE ARE NO INDICATIONS ON THIS PRPOSED DEMO PERMIT OF |
| | THE INTENTIONS OR NON-INTENTIONS TO HAVE THIS BUILDING |
| | OCCUPOED DURING DEMO NOR RECONSTRUCTION. |
| | |
| | PER NFPA |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, |
| | MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS |
| | AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND |
| | APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN |
| | SECTION 1.14. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDED A DETAILED NARRATIVE |
| | EXXPLAINING THE INTENT TO OCCUPY OR NOT ANF INCLUEDE |
| | LIFE SAFETY DETAILS TO ENSURE THE OCUPANCT ARE PROTECED |
| | AT ALL TIMES. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |