| 2023-03-03 10:20:49 | DOORS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DOOR (B146) IS IN WIND ZONE 5 PER DRAWING S0.06 | | | WHICH SHOWS A WIND PRESSURE OF (-176 X .6 = 105.6) - | | | PRODUCT APPROVAL NUMBER (20-0310.08) CONFIGURATION 1 | | | SHOWS A PRESSURE OF (-75) (+75) - WHICH DOES NOT MEET | | | THE REQUIRED WIND PRESSURE. | | | | | | 2) PLEASE PROVIDE THE FRONT PAGES OF THE STATE PRODUCT | | | APPROVAL FOR (FL16355.1) | | | | | | 3) THE ORIGINAL SIGNED AND SEALED PRIVATE PROVIDER | | | AFFIDAVIT NEEDS TO BE DELIVERED TO THE BUILDING | | | DIVISION. |
|