| Plan Review Notes For Permit 22111001 |
| Permit Number |
22111001 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-01-13 11:07:45 | 2ND REVIEW FMC | | | PERMIT: 22111001 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF | | | SPACE. THE OCCUPANCY CLASSIFICATION FROM TABLE | | | 403.3.1.1 MUST BE THE ONE THAT MOST RESEMBLES THE USE | | | OF THE SPACES AND YOU WILL NEED TO NAME THE SPACE PER | | | THE OCCUPANCY CLASSIFICATION CHOSEN FROM TABLE | | | 403.3.1.1. | | | | | | 2) PROVIDE A MENU FOR THIS TENANT SPACE. IS THERE TO BE | | | ANY COOKING OF MEATS OR OTHER FOODS THAT WOULD PRODUCE | | | COOKING VAPORS AND RESIDUES? FMC 507.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|