Plan Review Notes
Plan Review Notes For Permit 22111001
Permit Number 22111001
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-05 15:02:071ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.8 - DIRECT CONNECTION - THE
 DISCHARGE PIPING FROM A GREASE INTERCEPTOR SHALL BE
 DIRECTLY CONNECTED TO THE SANITARY DRAINAGE SYSTEM.
  
 2. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE SUBMIT THE
 DETAILS FOR THE GREASE INTERCEPTOR.
  
 3. 2017 WPB AMENDS 105.1 - THE GREASE INTERCEPTOR
 REQUIRES IT'S OWN SEPARATE PERMIT. IT IS REQUIRED TO BE
 SUBMITTED BEFORE THIS COMMENT CAN BE RELEASED. IF
 NECESSARY, YOU CAN SUBMIT A PERMIT APPLICATION FOR THE
 GREASE TRAP WITH THE CONTRACTOR LISTED AS "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, RESPOND TO THIS COMMENT IN A
 NARRATIVE AND I CAN RELEASE THE COMMENT.
  
 4. 2020 FPC 2020 FPC 1003.3.1 - THE FLOOR DRAIN AND THE
 SINGLE COMPARTMENT SINK IN THE FOOD PREP AREA IS
 SUBJECT TO FAT/OIL/GREASE WASTE AND SHOULD BE CONNECTED
 TO THE GREASE TRAP. IF YOU FEEL THE SINGLE COMPARTMENT
 SINK DOES NOT NEED TO GO TO GREASE WASTE, YOU CAN
 DETAIL IT'S USE.
  
 5. 2020 FPC 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER
 THIS SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  