Plan Review Notes
Plan Review Notes For Permit 22111001
Permit Number 22111001
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-12-01 10:39:11FIRE PROVISO COMMENTS:
  
 (1) DOOR LOCKING ARRANGEMENTS SHALL COMPLY WITH THE
 FOLLOWING:
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY
 FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY,
 A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION
 FROM THE
 EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO
 HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED
 THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43
 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 (2) PORTABLE FIRE EXTINGUISHERS SHALL BE OF THE
 APPROPRIATE SIZE AND TYPE FOR THE HAZARD AND MOUNTED IN
 A FIRE CODE COMPLIANT MANNER.
  