Plan Review Notes
Plan Review Notes For Permit 22110956
Permit Number 22110956
Review Stop M
Sequence Number 2
Notes
Date Text
2023-01-13 06:09:59THE OUTOOR AIR FOR THIS TENANT MUST BE CALCULATED BY
 SHOWING EACH USE OF SPACE IN THIS TENANT AND ITS
 MINIMUM REQUIRED OUTDOOR AIR FOR EACH. YOU CANNOT JUST
 PROVIDE A TOTAL USING THE SQUARE FOOTAGE AND ONE
 BLANKET OCCUPANCY CLASSIFICATION. PROVIDE A COMPLETE
 OUTDOOR AIR CALCULATION FOR THIS TENANT SPACE WHICH
 INCLUDES EACH OCCUPANCY SHOWN ON SHEET G-011. TABLE
 403.3.1.1 OF THE FMC MUST BE USED AND YOU MUST PICK AN
 OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN TERMS
 OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION. THE OCCUPANTS SHOULD BE BASED ON OCCUPANT
 DENSITYFROM TABLE 403.3.1.1, NOT THE EGRESS NUMBERS
 FROM THE ARCHITECT OR FROM ASHRAE 62.1.
 FMC 403.2 OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR
 AIRFLOW RATE SHALL BE DETERMINED IN ACCORDANCE WITH
 SECTION 403.3. FMC 403.3, 403.3.1.1 AND TABLE 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER