| Plan Review Notes For Permit 22110956 |
| Permit Number |
22110956 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-15 16:10:27 | 1ST REVIEW FMC | | | PERMIT: 22110956 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REVISE M2.1 AND THE VAV BOX UNIT SCHEDULE ON SHEET | | | M6.1 TO ALIGN, EXAMPLES: VAV-6-2; SHEET M2.1 HAS 2000 | | | CFMS BUT SHEET M6.1 HAS MAX. 1400 CFMS. VAV-6-4 IS NOT | | | SHOWN ON SHEET M2.1. PLEASE COMPARE EACH VAV. FBC | | | 107.3.5 | | | | | | 2) PROVIDE THE VENTILATION SCHEDULE FOR THIS TENANT | | | SPACE BASED ON EACH OCCUPANCY CLASSIFICATION AND | | | OCCUPANT DENSITY ACCORDING TO TABLE 403.3.1.1. FMC | | | 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|