| Plan Review Notes For Permit 22110952 |
| Permit Number |
22110952 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-29 09:22:56 | FIRE REVIEW COMMENTS: | | | | | | (1) THE PLAN SUBMITTAL DID NOT INDICATE THE DOOR | | | HANDLE/LOCKING ASSEMBLY THAT WOULD NOT REQUIRE THE USE | | | OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. NFPA 101, 7.2.1.5 | | | | | | (2) THE PLAN SUBMITTAL DID NOT INDICATE EMERGENCY | | | LIGHTING. NFPA 101, 7.9 | | | | | | | | | (3) THE PLAN SUBMITTAL DID NOT INDICATE MARKING THE | | | MEANS OF EGRESS. NFPA 101, 7.10 | | | | | | (4) FIRE SPRINKLER COVERAGE IS ADDRESSED BY PERMIT | | | #22090774. | | | | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|