| 2022-12-19 11:15:15 | RESIDENTIAL(R3), SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22110944 |
| | 530 36TH ST |
| | |
| | ORIGINAL COMMENT: |
| | 1- SURVEY SHOWS DOUBLE GATES (10 FOOT OPENING). NEED TO |
| | PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE |
| | DOUBLE GATE COMPLIES WITH THE SELF-CLOSING AND |
| | SELF-LATCHING REQUIREMENTS OF SEC. R4501.17.1.8 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | PROPOSED DOUBLE GATES WAS REVIEWED WITH RICHARD |
| | GATHRIGHT (ASSISTANT BUILDING OFFICIAL) FOR BUILDING |
| | CODE COMPLIANCE. PROPOSED DON'T SHOW HOW THE TWO |
| | OPERABLE GATES COMPLY WITH THE SELF-CLOSING AND |
| | SELF-LOCKING REQUIREMENTS. |
| | |
| | R4501.17.1.8 |
| | ACCESS GATES, WHEN PROVIDED, SHALL BE SELF-CLOSING AND |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS |
| | R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED |
| | WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON THE POOL |
| | SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED |
| | NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE |
| | GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON |
| | EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE |
| | REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY |
| | OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE |
| | ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM |
| | THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING |
| | GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457 |
| | MM) OF THE RELEASE MECHANISM. |
| | |