| 2022-12-08 07:12:31 | 2ND GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC G2439.5 - PER YOUR NOTE, A 10" ROUND DOES |
| | NOT PROVIDE 100 SQ. IN. OF MAKEUP AIR TO SATISFY THIS |
| | CODE SECTION. IF YOU ARE USING "ANOTHER APPROVED |
| | METHOD", YOU WILL NEED TO SHOW YOUR CALCULATIONS AND |
| | HOW YOU CAME UP WITH THE AMOUNT OF COMBUSTION AIR |
| | NEEDED. I AM UNABLE TO VERIFY THE CALCULATIONS BECAUSE |
| | THE PLANS DO NOT SHOW A FLOOR PLAN WHICH WOULD INCLUDE |
| | ROOM DIMENSIONS. YOU NEED TO DETAIL THE ROOM SIZE AND |
| | CALCULATIONS USED. |
| | |
| | 2. 2020 FRC G2439.5 - YOU WILL NEED TO SHOW A DETAIL |
| | SHOWING HOW YOU ARE ACHEIVING THE REQUIRED MAKEUP AIR. |
| | SHOW A SIMPLE FLOOR PLAN THAT SHOWS WHERE THE AIR IS |
| | COMING FROM, AND WHAT TYPE OF DUCTS OR GRILLS ARE BEING |
| | USED TO TRANSFER THE AIR INTO THOSE ROOMS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |