| 2022-12-12 16:44:16 | NEW GARAGE WITH GUEST UNIT ABOVE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) WIND DESIGN SHOWN USING EXPOSURE "C" - WITH THE |
| | LOCATION OF THE PROPERTY NEXT TO THE WATERWAY EXPOSURE |
| | "D" SHOULD BE USED - FBC R301.2.1.4.3 EXPOSURE D SHALL |
| | ALSO APPLY WHERE THE GROUND SURFACE ROUGHNESS |
| | IMMEDIATELY UPWIND OF THE SITE IS B OR C, AND THE SITE |
| | IS WITHIN A DISTANCE OF 600 FEET (183 M) OR 20 TIMES |
| | THE BUILDING HEIGHT, WHICHEVER IS GREATER, FROM AN |
| | EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS |
| | SENTENCE. |
| | |
| | 2) PLEASE SHOW THE REQUIRED ROOF CLADDING WIND |
| | PRESSURES PER FBC FIGURE R301.2(7) |
| | |
| | 3) PLEASE PROVIDE A SOIL REPORT - FBC R401.4 |
| | |
| | 4) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL |
| | FL15180.7 |
| | |
| | 5) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB |
| | 107.3.4 |
| | |
| | 6) PLEASE PROVIDE DETAILS FOR THE GUARD RAILING FBC R |
| | 312 |
| | |
| | 7) PLEASE PROVIDE DETAILS FOR THE STAIR HAND RAILS FBC |
| | R311.7.8 |
| | |
| | 8) FBC R311.7.5.1 OPEN RISERS ARE PERMITTED PROVIDED |
| | THAT THE OPENINGS LOCATED MORE THAN 30 INCHES (762 MM), |
| | AS MEASURED VERTICALLY, TO THE FLOOR OR GRADE BELOW DO |
| | NOT PERMIT THE PASSAGE OF A 4-INCH-DIAMETER (102 MM) |
| | SPHERE. |
| | |
| | 9) FBC R318.5 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 10) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING |
| | INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION |
| | DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT |
| | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE |
| | THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| | WATER RETAINING SWALES) |
| | |
| | 11) A SEPARATE PERMIT IS REQUIRED FOR THE SITEWALL. |
| | |
| | 12) STRUCTURAL DRAWINGS NEED TO BE SIGNED AND SEALED BY |
| | THE DESIGNER FBC 107 - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| | E-SIGNATURE). |
| | |