| 2023-02-14 16:07:46 | SEE COMMENTS FOR PERMIT 22080820 AS THE DRAWINGS ARE |
| | SUBMITTED IN THAT PERMIT SUBMITTAL. |
| | |
| | 4TH REVIEW FMC |
| | PERMIT: 22080820 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY CALCULATIONS SUBMITTED ARE FOR UNIT 434 |
| | BUT THIS PERMIT APPLICATION IS FOR UNIT 432. PROVIDE |
| | THE CALCULATIONS FOR UNIT 432. FBC 107.3.5 |
| | |
| | 2) ACCORDING TO THE MECHANICAL CONTRACTOR THAT HAD |
| | SUBMITTED THE ORIGINAL DRAWINGS, THESE TENANT SPACES |
| | WERE TO BE A CHANGE OF USE FROM STORAGE TO A PET |
| | GROOMER. THE COVER SHEET SUBMITTED STATES THIS IS STILL |
| | A STORAGE. PLEASE EXPLAIN. |
| | |
| | 3) ARE THE RTU???S LIKE FOR LIKE CHANGE OUTS? IF NOT |
| | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | REQUESTED IN PREVIOUS REVIEW COMMENTS. FEC C403.2.1 |
| | |
| | 4) PROVIDE A SITE PLAN SHOWING THE NEW BATH EXHAUST FAN |
| | TERMINATION LOCATION WILL MEET THE 10 FEET REQUIREMENTS |
| | FROM THE PROPERTY LINE. FMC 501.3.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |