| Plan Review Notes For Permit 22110878 |
| Permit Number |
22110878 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-01-10 17:08:55 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 22110878 UNIT #434 | | | 1/10/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #1 PRINTED BELOW | | | STILL EXISTS. THE REQUIRED SERVICE SINK IN UNIT 434 WAS | | | NOT PROVIDED. | | | | | | 1) SHEET A-1.2: PROVIDE PLUMBING FIXTURE CALCULATIONS | | | IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A | | | SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF | | | FIXTURES. THE PLAN SHOWS COMPLIANCE FOR THE NUMBER OF | | | WATER CLOSETS AND LAVATORIES, AND DRINKING FOUNTAINS | | | ARE NOT REQUIRED FOR OCCUPANT LOADS OF 15 AND UNDER, | | | HOWEVER A SERVICE SINK IS REQUIRED. PLEASE REVISE THE | | | PLANS TO SHOW THE SINK LOCATION AND PLUMBING PIPING | | | DETAILS- SEC. 107.2.1 & 107.3.5.1.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|