| Plan Review Notes For Permit 22110877 |
| Permit Number |
22110877 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-03 10:40:20 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. REVIEW THE ELECTRICAL PANEL SCHEDULE AND ELECTRICAL | | | LOAD CALCULATON TO BE IN ACCORDANCE WITH NEC NEC 220, | | | 408.4(A) AND . | | | A. SMOKE ALARMS (SMOKE DETECTION) AC POWER W/BATTERY | | | BACK UP, SMOKE DETERCTOR REQUIRED TO BE INTERCONNECTED | | | FBC R314.4 | | | B. SMALL APPLIANCE PER NEC 210.52 (B) | | | | | | 2. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER | | | NEC 440.14 OR IRC E4101.5 | | | DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN | | | SIGHT FROM AND READILY ACCESSIBLE??? FROM THE | | | AIR-CONDITIONING EQUIPMENT. | | | | | | 3. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|