2023-01-03 10:40:20FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW THE ELECTRICAL PANEL SCHEDULE AND ELECTRICAL
 LOAD CALCULATON TO BE IN ACCORDANCE WITH NEC NEC 220,
 408.4(A) AND .
 A. SMOKE ALARMS (SMOKE DETECTION) AC POWER W/BATTERY
 BACK UP, SMOKE DETERCTOR REQUIRED TO BE INTERCONNECTED
 FBC R314.4
 B. SMALL APPLIANCE PER NEC 210.52 (B)
  
 2. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER
 NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN
 SIGHT FROM AND READILY ACCESSIBLE??? FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 3. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11
 THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  