| 2023-01-04 12:41:37 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. PAGE P-101 -- 2020 FPC 914.1 - THE ISOMETRIC SHOWS |
| | THE UPSTAIRS GROUP'S STACK DISCHARGING TO THE HIGH SIDE |
| | OF THE CIRCUIT VENT THAT SERVES THE DOWNSTAIRS GROUP. A |
| | STACK CANNOT CONNECT TO THE CIRCUIT VENT. FIXTURES ARE |
| | ALLOW TO BE CIRCUIT VENTED WHEN CONNECTED TO A |
| | HORIZONTAL BRANCH DRAIN. THE CONNECTION OF A STACK AT |
| | THAT LOCATION TURNS THAT PORTION OF THE DRAIN INTO A |
| | BUILDING DRAIN. THE UPSTAIRS STACK WOULD NEED TO |
| | CONNECT DOWNSTREAM OF THE CIRCUIT VENT SYSTEM. |
| | |
| | 2. PAGE P-101 -- FD-2 - THE FLOOR DRAIN ON THE END OF |
| | THE RUN IS NOT VENTED. WHEN CONNECTED TO A BUIILDING |
| | DRAIN, IT NEEDS TO BE VENTED. |
| | |
| | 3. 2017 WPB AMENDS 107.3.5.1.3 - THE ROOF DRAINAGE |
| | APPEARS TO TERMINATE ONTO THE CANOPIES. I AM UNABLE TO |
| | LOCATE THE GUTTER/DOWNSPOUT SIZES FOR THE CANOPIES. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |