| Plan Review Notes For Permit 22110873 |
| Permit Number |
22110873 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-03 12:51:14 | 1ST REVIEW FMC | | | PERMIT: 22110873 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT. | | | FEC C401.2 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FEC C403.2.1 | | | | | | 3) SHEET LS-101; THE ELECTRICAL ROOM APPEARS TO HAVE 1 | | | HOUR RATED WALLS. SHEET M-101: PROVIDE FIRE DAMPERS ON | | | THE DRAWING FOR THE PENETRATIONS OF THE RATED WALLS | | | WITH THE MECHANICAL DUCTWORK. | | | | | | 4) SHEET M-101: SHOW THAT EF-05 AND EF-06 MEET THE CFM | | | REQUIREMENTS OF FMC TABLE 403.3.1.1 FOOTNOTE E | | | | | | 5) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS | | | BUILDING. FMC 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|