| 2022-12-12 14:51:48 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, |
| | FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE TABLE ON THE LIFE SAFETY PLAN INDICATES THIS |
| | BUILDING BEING CLASSIFIED AS MIXED, SEPARATED OCCUPANCY |
| | BUT YOU HAVE LISTED 0-HOUR SEPARATION ON THE TABLE. |
| | PLEASE CLARIFY THIS WITH THE REFERENCE TO THE FOLLOWING |
| | ACCORDING TO NFPA 101 CHAPTER 6, |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE OCCUPANCIES |
| | ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE BARRIERS. |
| | |
| | 2) CLARIFY THE ALREADY LISTED SEPARATION WITH THE |
| | REQUIREMENTS OF TABLE 6.1.14.4.1. |
| | |
| | 3) THERE ARE WINDOWS SHOW ON FIRE RATED WALLS WITH NO |
| | RATING. PLEASE INDICATE THE RATING OF THE WINDOWS. |
| | |
| | 4) A LIFE SAFETY PLAN MUST CLEARLY ILLUSTRATE THE |
| | COMMON PATH OF TRAVEL AND TRAVEL DISTANCES, PER NFPA |
| | 101 CHAPTER 7. |
| | |
| | 5) A GATE IS INDICATED ON THE PLANS PLEASE INDICATE THE |
| | PROVIDED FIRE DEPARTMENT ACCESS. |
| | |
| | 6) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE |
| | DONE BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP |
| | DRAWING COMPLIANT WITH NFPA 72 IS REQUIRED TO BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| | BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | |