| 2023-02-08 07:45:48 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE FLOOR PLAN OF HOME SHOWING EXISTING SERVICE |
| | EQUIPMENT AND PANEL LOCAITON AND NEW PROPOSED EXISTING |
| | SERVICE EQUIPMENT AND PANEL LOCATION. FBC 107.2.1 |
| | |
| | 2. REVISION REQUEST FORM SAYS "200/255" METER MAIN |
| | COMBO? THAT IS NOT AN ACCURATE DESCRIPTION. PLEASE |
| | UPDATE. |
| | |
| | 3. RISER DIAGRAM MUST SHOW WHETHER IT IS A SERVICE |
| | LATERAL OR OVERHEAD SERVICE ENTRANCE CONDUCTORS. ALSO |
| | SIZE OF SERVICE ENTRANCE CONDUCTORS ARE NOT SHOWN. FBC |
| | 107.2.1 NEC 215 NEC 230 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |