| Plan Review Notes For Permit 22110806 |
| Permit Number |
22110806 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-23 09:59:54 | FIRE PROVISO COMMENTS: | | | | | | (1) WITH THE REMOVAL AND/OR ADDITION OF WALLS, AN | | | EVALUATION SHALL BE MADE BY A QUALIFIED CONTRACTOR TO | | | ENSURE ADEQUATE COVERAGE IS MAINTAINED FOR ALL LIFE | | | SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE ALARM). | | | | | | (2) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY | | | PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS | | | AND SHOP DRAWINGS. | | | | | | (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL BE MAINTAINED AND OPERATIONAL | | | DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION. | | | | | | (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | | HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A | | | FIRE WATCH. | | | | | | (5) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL | | | DAMAGE INCLUDING PAINT DURING ALL PHASES OF DEMOLITION | | | AND CONSTRUCTION. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|