2022-11-23 09:59:54FIRE PROVISO COMMENTS:
  
 (1) WITH THE REMOVAL AND/OR ADDITION OF WALLS, AN
 EVALUATION SHALL BE MADE BY A QUALIFIED CONTRACTOR TO
 ENSURE ADEQUATE COVERAGE IS MAINTAINED FOR ALL LIFE
 SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE ALARM).
  
 (2) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE MAINTAINED AND OPERATIONAL
 DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (5) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL
 DAMAGE INCLUDING PAINT DURING ALL PHASES OF DEMOLITION
 AND CONSTRUCTION.
  