| 2022-11-18 07:12:54 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22110681 | | | 11/18/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PERMIT APPLICATION DOES INDICATE WHETHER THE | | | BACKFLOW REPLACEMENT IS FOR THE POTABLE WATER SERVICE | | | LINE OR FOR THE FIRE SERVICE LINE, ALTHOUGH IT APPEARS | | | TO BE FOR THE FIRE LINE BECAUSE IT IS A DCDA. PLEASE | | | CLARIFY AND NOTE AN RPZ BACKFLOW ASSEMBLY IS REQUIRED | | | FOR POTABLE WATER SERVICES- SEC. E- WPB UTILITIES CROSS | | | CONNECTION MANUAL. | | | | | | 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF | | | THE BACKFLOW- SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|