Plan Review Notes
Plan Review Notes For Permit 22110679
Permit Number 22110679
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-09 13:00:40ELECTRIC REVIEW FAILED
 1) APPLICATION AND ESTIMATE INDICATE NO ELECTRIC WORK
 IS TO BE DONE. PLEASE CLARIFY, AS PLANS INDICATE
 RECEPTACLES IN KITCHEN AND BATH AND A NOTE STATING
 KITCHEN TOP OUTLETS. FBC 107.2
  
 NOTE: PLEASE ENSURE IF ELECTRIC WORK IS TO BE DONE THAT
 PLAN INCATES CODE COMPLIANCE FOR ALL NEW WORK.
 INCLUDING RECEPTACLE SPACING, PROPER CIRCUITRY, TAPER
 RESISTANT RECEPTACLES, GFI AND ARC FAULT PROTECTION AS
 APPLICABLE AND OTHER NEC REQUIREMENTS AS APPLICABLE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  