| 2022-12-09 13:00:40 | ELECTRIC REVIEW FAILED | | | 1) APPLICATION AND ESTIMATE INDICATE NO ELECTRIC WORK | | | IS TO BE DONE. PLEASE CLARIFY, AS PLANS INDICATE | | | RECEPTACLES IN KITCHEN AND BATH AND A NOTE STATING | | | KITCHEN TOP OUTLETS. FBC 107.2 | | | | | | NOTE: PLEASE ENSURE IF ELECTRIC WORK IS TO BE DONE THAT | | | PLAN INCATES CODE COMPLIANCE FOR ALL NEW WORK. | | | INCLUDING RECEPTACLE SPACING, PROPER CIRCUITRY, TAPER | | | RESISTANT RECEPTACLES, GFI AND ARC FAULT PROTECTION AS | | | APPLICABLE AND OTHER NEC REQUIREMENTS AS APPLICABLE. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|