Plan Review Notes
Plan Review Notes For Permit 22110671
Permit Number 22110671
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-23 11:15:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22110671 GREASE INTERECEPTOR
 MP#22070634 4065 N HAVERHILL RD # B1
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. THE MASTER FOR THIS PROJECT PERMIT NUMBER 22070634
 HAS NOT BEEN APPROVED AS THERE AS THERE ARE UNRESOLVED
 COMMENTS TO THE PLUMBING DESIGN SUBMITTED FOR THIS
 PROJECT INCLUDING THOSE CONCERNING THE GREASE
 INTERCEPTOR. NOTE THAT THE MASTER PLUMBING DESIGN WHEN
 APPROVED AND THIS PERMIT SUBMITTAL SHALL BE RECONCILED
 WITH EACH OTHER FOR APPROVAL.
  
 2. PROVIDE CALCULATIONS AND STANDARD FOR SIZING OF THE
 GREASE INTERCEPTOR. FBC PL 1003.3.5
  
 3. PROVIDE FLOOR PLAN AND RISER DIAGRAM SHOWING
 LOCATION OF INTERCEPTOR, ITEMS DISCHARGING TO THE UNIT
 AND DRAINAGE PIPING
  
 4. SEE COMMENTS FROM MASTER PERMIT 2ND REVIEW
 CONCERNING THE GREASE INTERCEPTOR BELOW WHICH MUST BE
 RESOLVED.
 1A: ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4.
 2A: NEW COMMENT: CALCULATIONS FOR GREASE INTERCEPTOR
 SHALL NOT INCLUDE HAND SINKS. FBC PL 1003.2. IF MOP
 SINK AND PREP SINK DISCHARGE TO GREASY WASTE THEN THEY
 SHALL BE INCLUDED IN CALCULATIONS.
 3A: NEW COMMENT: GREASE TRAP SUBMITTAL DOES NOT
 INDICATE THE SIZE OF THE INTERCEPTOR TO BE USED. PLEASE
 INDICATE THE MODEL NUMBER/SIZE ON THE SUBMITTAL. THE
 INLET/OUTLET PORTS SHALL BE SIZED TO ACCOMMODATE IN
 SIZE OF THE INLET AND OUTLET SIZE OF THE PIPING. FBC PL
 704.2
 4A: NEW COMMENT: RISER DIAGRAM SHOWS A 2-WAY CLEANOUT
 UPSTREAM AND DOWNSTREAM OF THE INTERCEPTOR BUT THEY
 APPEAR TO BE A CROSS TEE IN THE DIAGRAM. PLEASE SHOW A
 2WAY CO TEE WITH A SMOOTH HORIZONTAL BOTTOM. A
 DEPRESSED/TRAPPED BOTTOM IS NOT ALLOWED
 5A: NEW COMMENT: PROVIDE VTR FOR GREASY WASTE SYSTEM.
 FBC PL 904.1, 904.1.1, 904.1.2
 6A: 22. PER 802.1, FLOOR DRAINS LOCATED WITHIN WALK-IN
 REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND FOOD
 ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO THE
 SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP.
 TO BE CLEAR, PROVIDE DETAIL
 NEW COMMENT: DOES THIS DRAIN CONTRIBUTE FAT, OIL OR
 GREASE (FOG) TO THE SYSTEM. IF SO, DISCHARGE THE
 RECEPTOR TO THE GREASY WASTE AND ADD TO THE
 CALCULATIONS FOR THE INTERCEPTOR. IF NOT, DISCHARGE TO
 SANITARY
 7A: 31. SECOND REQUEST: ICE MAKER(S), HAND SINKS, STEAM
 TABLE AND SERVICE SINKS SHALL NOT DISCHARGE TO THE
 GREASY WASTE PER FBC PL 1003.2.
 TO BE CLEAR, #11 STEAM TABLE, #2 ICE MAKER DRAIN, #4
 ICE MAKER DRAIN SHALL NOT DISCHARGE TO GREASE
 INTERCEPTOR. FBC PL 1003.2. IT IS DETERMINED THE #7 MOP
 SINK (SERVICE SINK) MAY DISCHARGE TO THE GREASE
 INTERCEPTOR.
 9A: NEW COMMENT: PROVIDE WASTE, HOT AND COLD WATER FOR
 #8 PREP SINK PER FBC PL 301.3, 602.2, 607.1; IS IT A
 FOOD PREP SINK? IF SO, COMPLY WITH FBC PL 802.1.1 OR
 801.1.7 AS APPLICABLE.
 IF THE WASTE CONTRIBUTES FAT, OIL OR GREASE (FOG) WASTE
 RECEPTOR SHALL CONNECT TO GREASY WASTE. IF NOT, CONNECT
 RECEPTOR TO SANITARY.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  