| Plan Review Notes For Permit 22110665 |
| Permit Number |
22110665 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-05 07:31:14 | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | (1) LOAD ON 147 DOES NOT INCLUDE 125% PER 625.41 | | | | | | 625.41 OVERCURRENT PROTECTION. | | | | | | OVERCURRENT PROTECTION FOR FEEDERS AND BRANCH CIRCUITS | | | SUPPLYING EQUIPMENT SHALL BE SIZED FOR CONTINUOUS DUTY | | | AND SHALL HAVE A RATING OF NOT LESS THAN | | | 125 PERCENT OF THE MAXIMUM LOAD OF THE EQUIPMENT. WHERE | | | NONCONTINUOUS LOADS ARE SUPPLIED FROM THE SAME FEEDER, | | | THE OVERCURRENT DEVICE SHALL HAVE | | | A RATING OF NOT LESS THAN THE SUM OF THE NONCONTINUOUS | | | LOADS PLUS 125 PERCENT OF THE CONTINUOUS LOADS. | | | | | | (2) FAULT CURRENT CALCULATION NEED FOR SERVICE. 110.24 |
|