| 2022-11-30 15:19:12 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22110660 |
| | 11/30/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS PLAN: THE PE GAS PIPE IS FOR OUTDOOR UNDERGROUND |
| | USE AND SHALL NOT BE INSTALLED WITHIN OR UNDER ANY |
| | BUILDING OR SLAB- SEC. G2415.17.1 FBC RES. EXCEPTION 3 |
| | ALLOWS THE PE TO BE INSTALLED UNDER OUTDOOR PATIOS, |
| | WALKAYS AND DRIVEWAYS. BASED ON THE ICC CODE COMMENTARY |
| | WHICH IS A RELAIBLE SOURCE FOR CLARIFICATION OF CODE |
| | SECTIONS, IT APPEARS THE COVERED PORCH DOES NOT MEET |
| | THE DEFINITON OF OUTDOOR PATIO.EXAMPLES GIVEN IN THE |
| | COMMENTARY SHOW PE ALLOWED UNDER "OPEN PATIOS" WHICH |
| | ARE SLABS WITHOUT ROOF STRUCTURES. IS THERE AN OPTION |
| | TO INSTALL THE PIPING BEYOND THE FOOTPRINT OF THE |
| | COVERED PORCH? |
| | |
| | 2) GAS PLAN: PROVIDE THE GAS PRESSURE FROM THE LP TANK |
| | TO THE 2ND STAGE REGULATORS AND FROM THE REGULATORS TO |
| | THE APPLIANCES- SEC. G2413.1 FBC RES. PLEASE LIST THE |
| | PIPE SIZING TABLES ON THE PLAN- SEC. G2413.4 FBC RES. |
| | |
| | 3) GAS PLAN: A SEPARATE PERMIT IS REQUIRED FOR |
| | INSTALLATION OF THE POOL HEATER- SEC. 105.1 WPB. PLEASE |
| | PLACE A NOTE ON THE PLAN. |
| | |
| | 4) GAS PLAN: THE GAS PLAN SHALL BEAR THE PRINTED NAME |
| | AND SIGNATURE OF THE CONTRACTOR OR QUALIFIER WHO |
| | PREPARED THE DRAWING- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |