| 2023-02-21 09:34:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22110655 |
| | ADD: 700 S ROSEMARY SUITE; ??? |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. FEB. 21ST/ 2023 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. PLEASE SEE ADDRESSING COMMENT. THE CITY |
| | ADDRESSING DIVISION ASSIGNS TENANT ADDRESSES. PLEASE |
| | CONFIRM AND E-MAIL DS_ [email protected] 561-805-6659. |
| | CONTACTING CITYPLACE AND GETTING LANDLORD APPROVAL MAY |
| | OR MAY NOT MEET CITY OF W.P.B. APPROVAL!!!!!!! |
| | 1ST COMMENT. PERMIT APPLICATION, THE SUITE # B8 DOES |
| | NOT MEET THE CITY STANDARD FOR ADDRESSING. 2020 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED. 2020 FBC-B 501.2 |
| | ADDRESS IDENTIFICATION. NEW AND EXISTING BUILDINGS |
| | SHALL BE PROVIDED WITH APPROVED ADDRESS IDENTIFICATION. |
| | PLEASE IDENTIFY LOCATION OF UNIT. |
| | |
| | 2)) 2ND REQUEST. PLEASE SEE ADDRESSING COMMENT. THE |
| | CITY ADDRESSING DIVISION ASSIGNS TENANT ADDRESSES. SEE |
| | ADDRESSING COMMENT MUST CONTACT ADDRESSING. |
| | TITLEBLOCK TO CORRECT THE TENANT IMPROVEMENT ADDRESS |
| | TENANT SPACE IN THE TITLE BLOCK ONCE THE CITY OF WEST |
| | PALM BEACH PROVIDES AN APPROVED ADDRESS. SEE NOTES |
| | UNDER THE ADDRESS PLAN REVIEW FOR COMMENTS. FL. |
| | ADMINISTRATIVE CODE 61G1-16.004. |
| | |
| | 3-5) COMPLIED. |
| | |
| | |
| | |
| | 6) COMPLIED, DEMO 22100811. |
| | |
| | 7) 2ND REQUEST. SHEET S00 WIND DESIGN LOADS THE SHOW |
| | 170 MPH VULT, IMPORTANCE FACTOR IS GIVEN AS 1.0 AND |
| | EXPOSURE AS C BUT THE PLANS STATE DESIGN PRESSURES ON |
| | COMPONENTS AND CLADDING IN ACCORDANCE WITH ASCE 7-16 |
| | CHAPTER 30 BUT THERE ARE NO WIND DESIGN PRESSURES GIVEN |
| | FOR THE WALL OPENINGS, THERE ARE SHOWN ROOF PRESSURES |
| | FOR ZONES 1, 2, & 3. . PLEASE ALSO CONSIDER THE HEIGHT |
| | FACTOR AND MULTIPLIERS. PLEASE ALSO PROVIDE THE |
| | COMPONENT & CLADDING PRESSURES IN VASD SINCE ALL |
| | PRODUCT APPROVALS ARE IN VASD. |
| | |
| | 8) SEMI-COMPLIED. SHEET A301 NOW SHOWS A MONOLITHIC |
| | FOOTER BUT THE STRUCTURAL SHEETS HAVE NOT BEEN UPDATED |
| | S1.00 DETAIL B NOR SHEET S3.00 DETAIL 2, THERE IS NO |
| | SUCH DETAIL, DETAIL 2 IS FOR ANCHORING TO THE SLAB |
| | ABOVE. . |
| | 1ST ROUND OF COMMENTS. SHEET A301 SHOWS A CUT AWAY |
| | SECTION OF THE NEW STOREFRONT SYSTEM. THE QUESTION IS |
| | ON SHEET A-300 & A-302 DETAIL 1 SHOWS THE NEW |
| | STOREFRONT WALL IN THE SAME LOCATION WITH FOOTER. THE |
| | NEW RECESSED AREA OF WALL DETAIL 4 ALSO SHOWS A |
| | RECESSED FOOTER, THIS WAS FORMALLY INTERIOR FLOOR |
| | SPACE, IS THERE A MONOLITHIC FOOTER FOR THE NEW STEEL |
| | 4X4 COLUMNS? 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. |
| | THIS BUILDING CONTAINS EITHER BOLTED AND OR WELDED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| | BRUNELLE AT 561-805-6670. |
| | |
| | 11) 2ND REQUEST, NO CONTRACTOR HAS BEEN SIGNED ON TO |
| | UPLOADED PRODUCT APPROVALS, NOR HAS THE COVERSHEET |
| | LISTED DEFERRED SUBMITTALS OF COMPONENTS & CLADDING |
| | UNTIL AFTER PERMIT ISSUANCE. |
| | |
| | COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS AND |
| | CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, |
| | |
| | 12)2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL |
| | HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 13)2ND REQUES. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 14) BUILDING PROVISO: DELEGATED ENGINEERING. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 15) 2ND REQUEST. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 16) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |