Plan Review Notes
Plan Review Notes For Permit 22110655
Permit Number 22110655
Review Stop B
Sequence Number 1
Notes
Date Text
2022-12-21 11:24:09WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110655
 ADD: 700 S ROSEMARY SUITE; ???
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) PERMIT APPLICATION, THE SUITE # B8 DOES NOT MEET THE
 CITY STANDARD FOR ADDRESSING. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. 2020 FBC-B 501.2 ADDRESS
 IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE
 PROVIDED WITH APPROVED ADDRESS IDENTIFICATION. PLEASE
 IDENTIFY LOCATION OF UNIT.
 2) TITLEBLOCK TO CORRECT THE TENANT IMPROVEMENT ADDRESS
 TENANT SPACE IN THE TITLE BLOCK ONCE THE CITY OF WEST
 PALM BEACH PROVIDES AN APPROVED ADDRESS. SEE NOTES
 UNDER THE ADDRESS PLAN REVIEW FOR COMMENTS. FL.
 ADMINISTRATIVE CODE 61G1-16.004.
 3) COVERSHEET: UNDER THE HEADING 7 JURISDICTION WRONG
 STREET ADDRESS, THAT GIVEN IS FOR PALM BEACH COUNTY
 BUILDING DEPARTMENT NOT THE CITY OF WEST PALM BEACH.
 4) SHEET LIFE SAFETY PLAN: NEW STORE FRONT GLAZING AND
 RECESSED DOUBLE DOOR ENTRY. NOTE AT ENTRY IS TAKING THE
 EGRESS CAPACITY FACTOR OF 0.15 INCHES. TO TAKE THIS
 FACTOR THE LIFE SAFETY PLAN SHOULD ALSO INCLUDE ALL
 FACTORS INVOLVED UNDER THE 2020 FBC-BUILDING CODE
 1005.3.2 EXCEPTION # 1.THE BUILDING IS TO BE COMPLETELY
 SPRINKLERED IN ACCORDANCE WITH 903.3.1.1 OR 903.3.1.2
 AND THE BUILDING SHALL HAVE AN EMERGENCY VOICE/ ALARM
 COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION
 907.5.2.2.
 5) SHEET A201 TOILET ROOM ELEVATIONS THE TOILET TISSUE
 DISPENSER IS MEASURED HORIZONTALLY FROM THE REAR
 RESTROOM WALL. PLEASE REFER TO THE 2020
 FBC-ACCESSIBILITY CODE SECTION. 604.7. THE TOILET PAPER
 DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES
 MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
 6) AE100 EXISTING CONDITIONS, KEY NOTE # 3 STATES THE
 LANDLORD HAS REMOVED THE EXISTING STOREFRONT, PLEASE
 PROVIDE THE DEMO-PERMIT FOR THIS WORK. FOR THE ADDRESS
 700 S. ROSEMARY THERE WAS ONLY ONE DEMO PERMIT PULLED
 FOR THE 700 BLOCK OF SOUTH ROSEMARY 22100811 FOR UNIT #
 124.
  
 7) SHEET S00 WIND DESIGN LOADS THE SHOW 170 MPH VULT,
 IMPORTANCE FACTOR IS GIVEN AS 1.0 AND EXPOSURE AS C BUT
 THE PLANS STATE DESIGN PRESSURES ON COMPONENTS AND
 CLADDING IN ACCORDANCE WITH ASCE 7-16 CHAPTER 30 BUT
 THERE ARE NO WIND DESIGN PRESSURES GIVEN. PLEASE ALSO
 CONSIDER THE HEIGHT FACTOR AND MULTIPLIERS. PLEASE ALSO
 PROVIDE THE COMPONENT & CLADDING PRESSURES IN VASD
 SINCE ALL PRODUCT APPROVALS ARE IN VASD.
 8) SHEET A301 SHOWS A CUT AWAY SECTION OF THE NEW
 STOREFRONT SYSTEM. THE QUESTION IS ON SHEET A-300 &
 A-302 DETAIL 1 SHOWS THE NEW STOREFRONT WALL IN THE
 SAME LOCATION WITH FOOTER. THE NEW RECESSED AREA OF
 WALL DETAIL 4 ALSO SHOWS A RECESSED FOOTER, THIS WAS
 FORMALLY INTERIOR FLOOR SPACE, IS THERE A MONOLITHIC
 FOOTER FOR THE NEW STEEL 4X4 COLUMNS? 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 9) NEITHER A301 OR S100 DETAIL B SHOW IF THE NEW STEEL
 COLUMNS ARE TO CONTINUE TO THE DECK ABOVE AND ANCHOR
 INTO THE FLOOR/ CEILING DECK ABOVE? SHEET S300 DETAIL 2
 DOES NOT DESIGNATE IF THIS IS STEEL COLUMN OR METAL
 STUD INFILL. THE PLANS ARE ALSO SILENT IF THE STEEL
 STUD INFILL ARE ARCHITECTURAL OR STRUCTURAL. THERE IS A
 NOTE STOREFRONT SYSTEM BY DELEGATE ENGINEER. PLEASE
 PROVIDE ADDITIONAL INFORMATION. 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 10) WELDED OR BOLTED CONNECTIONS. THIS BUILDING
 CONTAINS EITHER BOLTED AND OR WELDED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
 11) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
 12) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 13) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 14) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
 15) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 16) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  