| 2022-12-28 10:46:39 | 1ST REVIEW FMC |
| | PERMIT: 22110652 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ADD A NOTE TO THE KITCHEN HOOD DRAWINGS STATING THAT |
| | THE KITCHEN HOODS AND GREASE DUCT WILL REQUIRE A |
| | SEPARATE PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS |
| | THEY WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 2) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT |
| | THE REFRIGERATION FOR THIS PROJECT WILL REQUIRE A |
| | SEPARATE PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS |
| | THEY WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC C403.2.1 |
| | |
| | 4) SHEET M-201A: THE NOA???S MENTIONED IN NOTES 13 AND |
| | 14 MUST BE ON THE JOBSITE FOR THE INSPECTOR AT TIME OF |
| | INSPECTION. |
| | |
| | 5) SHEET M-301: PLEASE UPDATE THE VENTILATION |
| | CALCULATIONS TO REFLECT THE CURRENT CODE AND SECTION OF |
| | THE CODE. 2020 FMC TABLE 403.3.1.1 |
| | |
| | 6) PLEASE PROVIDE A DETAIL FOR THE HP-2 RETURN AIR. THE |
| | HP-2 IS LOCATED IN THE KITCHEN BUT IT???S SERVING THE |
| | BAR AREA. PLEASE SHOW THAT NO RETURN AIR IS COMING FROM |
| | THE KITCHEN FOR THIS UNIT. FMC 601.5 NUMBER 7 |
| | |
| | 7) SHEET M-201A: PROVIDE A DETAIL DRAWING SHOWING THE |
| | INTAKE DUCT LOCATION, ARE THEY TO BE LOCATED ON THE |
| | ROOF? IF LOCATED IN THE COVERED WALKWAY THIS AREA IS |
| | CLOSED ON 3 SIDES AND WOULD NOT BE ABLE TO BE USED FOR |
| | OUTSIDE AIR INTAKE. FBC 107.3.5 |
| | |
| | 8) PLEASE SHOW HOW ALL OF THE MECHANICAL SYSTEMS, |
| | INCLUDING THE AHUS, WILL MEET THE SMOKE DETECTOR |
| | REQUIREMENTS FOR THE COMMON SUPPLY SYSTEMS. FMC 606.2.2 |
| | |
| | 9) SHOW HOW THE AHUS WILL BE SUPPLIED WITH THE REQUIRED |
| | OUTDOOR AIR. FMC 403.3.1.1 |
| | |
| | 10) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH |
| | ZONE. FMC 403.3.1.1.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |