| Date |
Text |
| 2022-12-13 10:48:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE EXIT SIGNS ON THE LIFE SAFETY SHEET; A |
| | 061.00, HOWEVER, THERE ARE NO EXIT SIGNS ON ANY |
| | ELECTIRCAL SHEET. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES |
| | |
| | 12.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE |
| | WITH CHAPTER 7 AND |
| | THIS CHAPTER. |
| | |
| | 12.2.10 MARKING OF MEANS OF EGRESS. |
| | 12.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS |
| | IN ACCORDANCE |
| | WITH SECTION 7.10. |
| | |
| | PLEASE REVIEW AND PROVIDE THE APPLICABLE EXIT SIGNAGE |
| | ON THE ELECTICAL PLAN SHEETS. |
| | |
| | |
| | 1A) THERE IS AN INDICATION OF A DOUBLE SWING DOOR; |
| | D112, WITH AN EXIT SIGN OVER THE MIDDLE OF IT. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY VISIBLE |
| | SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| | EXIT IS NOT READILY |
| | APPARENT TO THE OCCUPANTS. |
| | |
| | PLEASE ENSURE THAT THE EXIT SIGN IS MOVED TO ONE SIDE |
| | IN THE DIRECTION OF TRAVEL, NOT INSTALLED OVER THE |
| | MIDDLE, PER THE REQUIREMENT. |
| | |
| | |
| | 2) SHEET D 103.00 THRU D 107.00 - THERE ARE INDICATIONS |
| | OF DEMOLITION. |
| | |
| | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING |
| | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP |
| | DRAWINGS. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE DEMO SHEETS. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | THE KITCHEN HOOD & SUPPRESSION SYSTEMS SHALL BE |
| | INSTALLED UNDER SEPARATE PERMITS & SHOP DRAWINGS. |
| | |
| | |
| | THE EXIT SIGN OVER THE DOUBLE SWING DOOR; D112, IS |
| | REQUIRED TO BE OVER ONE SIDE OF THE DOOR, NOT IN THE |
| | MIDDLE. |