| 2023-04-20 12:33:39 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R37 |
| | (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| | WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| | CONSIDER USING FL5259-R38 (NON-HVHZ). |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R38 |
| | (NON-HVHZ) COVERS MULTIPLE PRODUCT TYPES; ROOF COVER |
| | OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS, ALLOWABLE SUBSTRATES & ATTACHMENT |
| | LIMITATIONS. SELECT PRODUCT TYPES, ALLOWABLE |
| | UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS & ATTACHMENT |
| | LIMITATIONS TO BE USED; SELECT FROM TABLE 4A |
| | DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS |
| | OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF |
| | APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. |
| | 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL6332-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: COVER SHEET |
| | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT). SECOND REQUEST. |
| | 4. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| | USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | PLEASE NOTE: CONCRETE/CLAY TILES; ASPHALT SHINGLES CAN |
| | NOT BE IN INSTALLED ON ROOFS WITH A ROOF SLOPE LESS |
| | THAN 2:12. SUBMIITED ROOF DRAWING LIST ROOF SLOPE AS |
| | 1:12. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |