| 2023-07-19 15:02:46 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22110628 |
| | 7/19/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE NOTE A COMPLETE |
| | REVIEW OF THE PLUMBING SYSTEMS WAS NOT PERFORMED UNDER |
| | THIS FOUNDATION PERMIT, AND ADDITIONAL COMMENTS |
| | IMPACTING THE UNDERGROUND PIPING SYSTEMS MAY OCCUR |
| | UNDER THE MAIN PERMIT REVIEW. |
| | |
| | 1) SHEET P200.1, P200.3, P200.5, P402A: BASED ON THE |
| | SCHIER SI & GI SPECIFICATIONS SHOWN ON THE DERM SHEETS |
| | THE GREASE INTERCEPTOR INLET AND OUTLET PIPINGS SHALL |
| | BE 4-INCH- SEC. 1003.3.5.1 FBC P. THE PLANS SHOW 3-INCH |
| | FOR FOG SYSTEMS #1 & 3. |
| | |
| | 2) BUILDING A GROUND FLOOR SHEETS P200.1, .2, .3, .4, |
| | .5, .6: AS PREVIOUSLY REQUESTED IN THE 1ST AND 2ND |
| | REVIEWS PLEASE SHOW THE FOLLOWING ITEMS. |
| | |
| | A) DFU'S FOR SANITARY PIPING AT RISERS, BRANCHES AND |
| | MAIN BUILDING DRAINS- TABLE 710.1(1) FBC P. |
| | |
| | B) STORM DRAINAGE FLOW IN GPM FOR EACH STORM DRAIN |
| | BRANCH AND MAIN- TABLE 1106.2 FBC P. |
| | |
| | C) AC CONDENSATE AND WATER HEATER DISCHARGE VERTICAL |
| | RISER LOCATIONS AND HORIZONTAL UNDERGROUND PIPING RUNS |
| | AND TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, |
| | 504.7.2 FBC P. |
| | |
| | D) EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL |
| | PROTECTION METHOD- SEC. 1002.4 FBC P. |
| | |
| | 3) 2ND REQUEST FOR GREASE INTERCEPTOR PERMIT |
| | APPLICATIONS. |
| | |
| | PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE GREASE |
| | INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR |
| | TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT |
| | APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected]. YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND |
| | THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA |
| | EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | A) SHEET P402A: 2ND REQUEST TO SHOW VENTING FOR THE |
| | INTERCEPTORS- SEC. 1003.9 FBC P. |
| | |
| | B) P9.00- P905 DERM SHEETS: 2ND REQUEST TO PROVIDE |
| | HEAVY DUTY LIDS FOR THE INTERCEPTOR CLEANOUTS. PLEASE |
| | PROVIDE MANUFACTURER AND MODEL NUMBER OF THE LIDS- SEC. |
| | 305.7 FBC P. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |