| 2023-05-17 16:00:41 | ELECTRIC REVIEW FAILED 2ND CYCLE |
| | |
| | 1) SUBMITTAL DOES NOT INCLUDE ALL DRAWINGS INDICATED ON |
| | PLAN INDEX SHEET CS001. MISSING DRAWINGS INCLUDE ALL |
| | ELECTRICAL DRAWINGS E202.1 -E202.8 . THESE DRAWINGS ARE |
| | ALSO REFERENCED ON SHEET E200. |
| | |
| | 2) PLEASE PROVIDE SHEETS LABELED E200.1 AND E200.3 |
| | (SECTIONS OF BUILDING A). FBC 107.2 |
| | |
| | 3) SHEET E501B, CORRECTLY LABELED, ELECTRICAL RISER |
| | DIAGRAM BUILDING A, AND IS AGAIN LABELED BELOW THE |
| | DIAGRAM AS BUILDING B. IN ADDITION THE SUBMITTAL NAME |
| | IS CALLED OUT INCORRECTLY AS RISER B. PLEASE CORRECT AS |
| | APPLICABLE. FBC 107.2 |
| | |
| | 4) PLEASE CORRECT LABELING FOR SHEET E502A SUBMITTAL |
| | NAME INDICATES RISE INSTEAD OF CORRECTLY NAMING |
| | ELECTRIC CALCS AND RISER NOTES |
| | |
| | 5) PLEASE ENSURE ALL SHEET NAMES ARE CORRECTLY LABELED |
| | ON SHEETS AND SUBMITTAL NAMING. FBC 107.2 |
| | |
| | 6) PLEASE PROVIDE ELECTRIC RISER DIAGRAM FOR BUILDING |
| | C. FBC 107.2 |
| | |
| | 7) PLEASE PROVIDE INDICATIONS THAT ALL OVERCURRENT |
| | PROTECTION RATED 1200 AMPS AND ABOVE CONTAIN ARC ENERGY |
| | REDUCTION METHOD IN ACCORDANCE WITH NEC 240.87 (A) AND |
| | (B) |
| | |
| | 8) PLEASE PROVIDE INDICATIONS THAT ALL FEEDER |
| | DISCONNECTS RATED 1000 AMPS AND ABOVE, FOR SYSTEMS OF |
| | MORE THAN 150 VOLTS TO GROUND ARE PROVIDED WITH GROUND |
| | FAULT PROTECTION. NEC 215.10 NEC |
| | |
| | 9) PLEASE PROVIDE FLOOR PLANS FOR BOTH ELECTRIC ROOMS |
| | IN BUILDING A, B AND C LOCATING ALL ELECTRICAL |
| | EQUIPMENT AND INDICATING ALL CLEARANCES REQUIRED IN |
| | ACCORDANCE WITH NEC 110.26 ARE MET. FBC 107.2 |
| | |
| | 10) PLEASE PROVIDE FLOOR PLANS FOR FIRE PUMP ROOM IN |
| | BUILDING A LOCATING ALL EQUIPMENT AND INDICATING ALL |
| | REQUIREMENTS OF NEC ARTICLE 695 ARE MET. FBC 107.2 |
| | |
| | 11) PLEASE PROVIDE FLOOR PLANS FOR GENERATOR ROOM IN |
| | BUILDING A LOCATING ALL EQUIPMENT AND INDICATING ALL |
| | REQUIREMENTS OF NEC ARTICLE 700, 445 AND CLEARANCES IN |
| | ACCORDANCE TO NEC 110.26. FBC 107.2 |
| | |
| | 12) PLEASE PROVIDE A NOTE STATING ALL LOW VOLTAGE |
| | WIRING SYSTEMS INCLUDING BUT NOT LIMITED TO FIRE ALARM, |
| | VOICE, DATA TELEPHONE, TV, SATELLITE, SECURITY AND BDA, |
| | DAS, CELL PHONE ENHANCEMENT SYSTEMS REQUIRE A SEPARATE |
| | PERMIT. IN ADDITION, SITE LIGHTING AND SIGNS WILL BE |
| | REQUIRED TO BE SEPARATE PERMITS |
| | |
| | 13) PLEASE PROVIDE A FEEDER SCHEDULE FOR ALL RISER |
| | DIAGRAMS. NEC 215.5 |
| | |
| | 14) SUBMITTAL CONTAINS SOME ELECTRIC SHEETS THAT HAVE A |
| | RED X ON THEM. IF THESE SHEETS ARE NOT INCLUDED WITH |
| | THE SUBMITTAL PLEASE HAVE THEM REMOVED. FBC 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |